Wiska Catalogue 2024
Impact Resistance
Degrees of protection acc. to EN 50102 / VDE 0470 P.100 Standard EN 50102 / VDE 0470 P.100 "Degrees of protection against external mechanical loading provided by enclosures for electrical apparatus (equipment) - IK-Code "is a classification system relating to the protection of electrical enclosures against external stress and damage.
JOINTS BRACE SYSTEM CABLE GLANDS CABLE ENTRIES ENCLOSURES JUNCTION BOXES TECHNICAL DATA LIGHTING
These IK-Codes used to categorise stress energy levels are as follows:
IK-Code
IK00
IK01
IK02
IK03
IK04
IK05
IK06
IK07
IK08
IK09
IK10
Stress energy in Joule
*)
0.15
0.2
0.35
0.5
0.7
1
2
5
10
20
*) not protected in conformity with the present standard.
Properties of Plastic employed (Selection)
Polyamide reinforced glass
Polypropylene reinforced glass
Polyethylen low density
Polyethylen high density
Material designation
Polyamide
Polypropylene
Polystyrene
Material shortmark
PA
PA-GF
PP
PP-GF
PE/LD
PE/HD
PS
Chemical resistance
Alcohol
A
A
A
A
A
A
A
Benzine
A
A
B
B
B
A
C
Diesel oil
A
A
A
A
B
B
C
Mineral oil
A
A
A
A
B
A
B
Animal and veg grease
B
B
A
A
A
A
B
Weak alkaline solution
A
A
A
A
A
A
A
Strong alkaline solution
A
A
A
A
A
A
A
Weak acids
A
A
A
A
A
A
A
Strong acids
B
B
B
B
B
A
B
Water
A
A
A
A
A
A
A
Susceptibility to stress cracking
Low
Low
Low
Low
Low
Low
Relatively high
Halogen free
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Phosphate free
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Silicone free
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Temperature range
Minimal
-40°C
-40°C
-30°C
-30°C
-40°C
-40°C
-25°C
Max. continually
100°C
100°C
80°C
100°C
80°C
80°C
60°C
Max. intermittent
120°C
150°C
100°C
120°C
100°C
100°C
80°C
Combustibility
UL 94 V-2
UL 94 HB
UL 94 HB
UL 94 HB
UL 94 HB
UL 94 HB
UL 94 HB
Thermal value (Hu) [kJ/kg]
32.000
32.000
46.000
46.000
46.000
46.000
42.000
Tel: 01208 816062 / info@wiska.co.uk / www.wiska.co.uk Other technical data on request / Subject to modifications and amendments
157
Made with FlippingBook Digital Proposal Maker