SWA Catalogue 2019
Cable terminations
Pre-insulated terminals
Crimping Procedure for Pre-insulated Terminals
A Cut wire to length B Strip the wire ends, ensuring the insulation is removed cleanly and square with the axis with no breaking or nicking of visible wire ends C Use the recommended stripped length appropriate to the connector being used, ensuring all strands are inserted fully into the crimp barrel D Ensure the selected crimp die is suitable for the correct combination of conductor and terminal being used E Insert conductor, stripped, to a length that leaves approximately 1mm visible at front of barrel F Position the die such as to leave approximately 1mm of barrel to form a bell mouth at the front of the barrel G Check the correct dot code or die identification is being used H Ensure the tool and dies are calibrated and maintained in a serviceable condition in line with SWA’s operating instructions
E
C
B
A
D
G
F
E
To see a video explaining techniques and best practice scan the QR code
CALL 01453 844 333 OR EMAIL sales@swaonline.co.uk 16