Manrose Ventilation Brochure
Technical specifications
Electrical 220-240V~50Hz AC single phase. All wiring must comply with current IEE regulations. A double pole isolating switch, having a contact separation of at least 3mm in all poles, must be used with a 3amp fuse fitted. Motor Motors are single phase external rotor design with capacitor start to optimise efficiency. HOT SPOT protection protects the motor from damage due to overheating/overloading. Sealed for life bearings ensure maintenance free operation.
Performance m 3 /hr
Sound dB(A) @ 3m
Model
Speed Rpm
Power Watts
MET100 MET125 MET150 MET200 MET250 MET315
1990 1907 2409 2505 2505 2370
277 388 759 788 817
42 44 62 96 94
47 47 51 50 53 61
1339
205
Performance
Construction Spun steel case featuring an
600
600
aerodynamically designed airflow guide vane. 30mm inlet and discharge spigot for ease of installation.
500
500
400
technical details
400
Installation Induct fans suitable for in-line and designed for use with suspended ceiling systems.
300
300
6
5
Pressure Pa
Pressure Pa
200
200
3 4
1
100
100
2
Speed Controller Cat No. METCON
0
0
0.1
0.2
0.3
0.4
0
0.1
0.2
0.3
0
Volume m 3 /s
Volume m 3 /s
Size
100
125
150
200
250
315
1
2
3
4
5
6
Dimensions
Product Size ØA
B
C
ØD
E
kg
MET100 MET125 MET150 MET200 MET250 MET315
100 125 150 200 250 315
206 206 227 227 230 247
167 175 175 175 170 179
245 245 345 345 345 400
290 290 390 390 390 445
3 3 4
4.5 4.5 6.5
Installation
E
ØA
ØD
C
B
81
Made with FlippingBook flipbook maker