Kosnic Evolve 7 2024 Brochure

Emergency lighting spacing table guide

Lumen : 140lm Lumen (w/ Flush Mounted Exit Sign) : 60lm Lumen (w/ Hanging Exit Sign) : 90lm

Manot MAN0305 Emergency Mode

Escape Route 2m wide (1 lux minimum)

Open (anti-panic) area (0.5 lux minimum)

a

b

a

b

a

b

a

b

Mounting Height (m)

Lux Level directly under*

Transverse to wall (m)

Transverse to transverse (m)

Axial to wall (m)

Axial to axial (m)

Transverse to wall (m)

Transverse to transverse (m)

Axial to wall (m)

Axial to axial (m)

Luminaire Type

Without Exit Sign

2.5m 8.73 lux

3.2m 8.1m 3.2m 8.2m

4m 9.89m 4.1m 10.1m

MAN0305

3m 6.05 lux

3.3m 8.7m 3.4m 8.8m 4.3m 10.7m 4.3m 10.9m

4m 4.44 lux

3.4m 9.1m 3.4m 9.2m 4.5m 11.4m 4.5m 11.6m

With Flush Mounted Exit Sign

2.5m 3.74 lux

3m

6.2m

3m

6.1m

3m

7.7m

3m

7.8m

MAN0305

3m 2.59 lux

3m

6.3m

3m

6.4m 3.1m 8.2m 3.1m 8.3m

44mm 1.90 lux

3m

6.4m

3m

6.5m 3.2m 8.6m 3.2m 8.7m

With Hanging Exit Sign

2.5m 5.62 lux

3m

7m

3m

7.1m 3.5m 8.7m 3.5m 8.89m

MAN0305

3m 3.89 lux

3m

7.4m

3m

7.5m 3.7m 9.39m 3.7m 9.5m

4m 2.85 lux

3m

7.7m

3m

7.8m 3.8m 9.89m 3.8m 10m

Lumen : 160lm Lumen (w/ Exit Sign) : 80lm

Mulu MUL0105 Emergency Mode

Escape Route 2m wide (1 lux minimum)

Open (anti-panic) area (0.5 lux minimum)

a

b

a

b

a

b

a

b

Mounting Height (m)

Lux Level directly under*

Transverse to wall (m)

Transverse to transverse (m)

Axial to wall (m)

Axial to axial (m)

Transverse to wall (m)

Transverse to transverse (m)

Axial to wall (m)

Axial to axial (m)

Luminaire Type

Without Exit Sign

2.5m 11.8 lux

3.5m 8.5m 3.6m 9.2m 4.3m 10.3m 4.5m 11.3m

MUL0105

3m 8.16 lux

3.7m 9.2m 3.8m 9.8m 4.6m 11.2m 4.8m 12.2m

4m 5.98 lux

3.8m 9.7m 3.9m 10.3m 4.9m 12m 5.1m 12.9m

With Exit Sign

2.5m 4.34 lux

3m

6.2m

3m

6.5m 3.1m 7.8m 3.2m 8.3m

MUL0105

3m 3.01 lux

3m

6.5m

3m

6.8m 3.3m 8.39m 3.3m 8.8m

44mm 2.2 lux

3m

6.7m

3m

6.9m 3.4m 8.8m 3.4m 9.2m

97

Made with FlippingBook flipbook maker