Kosnic Evolve 7 2024 Brochure
Emergency lighting spacing table guide
Lumen : 140lm Lumen (w/ Flush Mounted Exit Sign) : 60lm Lumen (w/ Hanging Exit Sign) : 90lm
Manot MAN0305 Emergency Mode
Escape Route 2m wide (1 lux minimum)
Open (anti-panic) area (0.5 lux minimum)
a
b
a
b
a
b
a
b
Mounting Height (m)
Lux Level directly under*
Transverse to wall (m)
Transverse to transverse (m)
Axial to wall (m)
Axial to axial (m)
Transverse to wall (m)
Transverse to transverse (m)
Axial to wall (m)
Axial to axial (m)
Luminaire Type
Without Exit Sign
2.5m 8.73 lux
3.2m 8.1m 3.2m 8.2m
4m 9.89m 4.1m 10.1m
MAN0305
3m 6.05 lux
3.3m 8.7m 3.4m 8.8m 4.3m 10.7m 4.3m 10.9m
4m 4.44 lux
3.4m 9.1m 3.4m 9.2m 4.5m 11.4m 4.5m 11.6m
With Flush Mounted Exit Sign
2.5m 3.74 lux
3m
6.2m
3m
6.1m
3m
7.7m
3m
7.8m
MAN0305
3m 2.59 lux
3m
6.3m
3m
6.4m 3.1m 8.2m 3.1m 8.3m
44mm 1.90 lux
3m
6.4m
3m
6.5m 3.2m 8.6m 3.2m 8.7m
With Hanging Exit Sign
2.5m 5.62 lux
3m
7m
3m
7.1m 3.5m 8.7m 3.5m 8.89m
MAN0305
3m 3.89 lux
3m
7.4m
3m
7.5m 3.7m 9.39m 3.7m 9.5m
4m 2.85 lux
3m
7.7m
3m
7.8m 3.8m 9.89m 3.8m 10m
Lumen : 160lm Lumen (w/ Exit Sign) : 80lm
Mulu MUL0105 Emergency Mode
Escape Route 2m wide (1 lux minimum)
Open (anti-panic) area (0.5 lux minimum)
a
b
a
b
a
b
a
b
Mounting Height (m)
Lux Level directly under*
Transverse to wall (m)
Transverse to transverse (m)
Axial to wall (m)
Axial to axial (m)
Transverse to wall (m)
Transverse to transverse (m)
Axial to wall (m)
Axial to axial (m)
Luminaire Type
Without Exit Sign
2.5m 11.8 lux
3.5m 8.5m 3.6m 9.2m 4.3m 10.3m 4.5m 11.3m
MUL0105
3m 8.16 lux
3.7m 9.2m 3.8m 9.8m 4.6m 11.2m 4.8m 12.2m
4m 5.98 lux
3.8m 9.7m 3.9m 10.3m 4.9m 12m 5.1m 12.9m
With Exit Sign
2.5m 4.34 lux
3m
6.2m
3m
6.5m 3.1m 7.8m 3.2m 8.3m
MUL0105
3m 3.01 lux
3m
6.5m
3m
6.8m 3.3m 8.39m 3.3m 8.8m
44mm 2.2 lux
3m
6.7m
3m
6.9m 3.4m 8.8m 3.4m 9.2m
97
Made with FlippingBook flipbook maker