Kosnic 2025 Evolve 8 Brochure

LED indicator reporting patten

LED Indicator (System status is locally indicated by a bi-coloured LED indicator)

Standard & Self-test 2 in 1 Standard Mode Self-test Mode

LED Indicator

Description

Status

Standard

DALI-2 Note

Flash Continuous On

Off On

Green Permanently On

System Healthy

Permanently Off

Emergency Mode

Off

2 s

2 s

Green Slow Flash (2s on-0.5s off) Green Slow Flash (0.5s on-0.5s off)

Battery Charging

N/A

1/2 s

Duration Test Pending Duration Test Running Functional Test Running Battery Charging Fault

1/2 s

Green Medium Flash (0.25s on-0.25s off) Green Fast Flash (0.125s on-0.125s off)

1/4 s

1/8 s

Red Permanently On

Red Medium Flash (0.25s on-0.25s off)

Battery Duration Fault

1/4 s

Red Fast Flash (0.125s on-0.125s off)

Lamp or Luminaire Fault

1/8 s

5 s

1 s

Green Stay On 5s Off 1s then Red On 1s Off 1s Off 1s then Green Fast Flash 5s (0.125s on-0.125s off) Off 1s then Green/Red Fast Flash 5s (0.125s on-0.125s off)

Installation Fault Warning

N/A

1 s

1 s

For 2 in 1 no DIP switch version For 2 in 1 no DIP switch version

1/8 s flash for 5 s

Standard mode

N/A

N/A

N/A

1/8 s flash for 5 s

Self-Test mode

N/A

N/A

N/A

26 Weeks Duration Test Interval 52 Weeks Duration Test Interval

5 s

Off 1s then Red Stay On 5s

N/A

N/A

N/A

Off 1s then Red Fast Flash 5s (0.125s on-0.125s off) Green Fast Flash Twice (0.1s on-0.1s off) then Off 1s

1/8 s flash for 5 s

N/A

N/A

N/A

1/10 s

Inhibit Mode Activated

N/A

N/A

N/A

1 s

1 s

1 s

Functionality of the test button (The test button enables you to make a series of settings manually)

Standard & Self-test 2 in 1 Standard Mode Self-test Mode

Description

Actions on test button

Function

Standard

DALI-2 Note

For 2 in 1 no DIP switch version

Set the test mode (Standard/Self-test)

< 2s

< 2s

N/A

N/A

Triple press <2s

Confirm the current duration test interval and 1s functional test

< 1s

< 1s

N/A

N/A

N/A

Press <1s

< 1s

< 1s

N/A

N/A

N/A

Double press <1s

Set the duration test interval

1-2s

1-2s

Press 1-2s

Manual functional test

5-10s

5-10s

Press 5-10s

Manual duration test

Double press <1s during emergency mode

< 1s

< 1s

Rest mode activated

62