SWITCHGEAR & DISTRIBUTION
Glasgow Fuse-Switch-Disconnectors & Switch-Disconnectors Switch Disconnectors
Glasgow Fuse-Switch-Disconnector
Part No. Poles Nominal Unit Rating, Ie (A) • Units are fitted with HRC Fuselinks of maximum rating but will accept fuselinks of a lower rating • SPSN and TPSN indicate switched neutral • Neutral makes first and breaks last
Eaton 415V Fuse(s) Fitted
Suitable Fuselinks
Copper Switch Links Fitted
Motor Ratings AC23A Ue 415V kW HP
All units are supplied with fuselinks or switchlinks fitted.Glasgow fuse switch disconnectors and switch disconnectors meet the constructional requirements for isolation of and are type tested to BS EN 60947-3. Five frame sizes are available to provide a range from 63A to 800A, with utilisation category AC22A and AC23A Ue 415V ratings. All units have retractable operating handles which drive overcentre mechanisms incorporating powerful operating springs. Flag “on-off” indication is provided and terminal cover shields prevent contact with live metal. Surface-mounting enclosures comprise heavy gauge steel body plates incorporating cast iron frame members and are rustprotected, with a light grey paint finish (RAL7004). Front access doors, which are detachable, are fitted with dust-excluding gaskets and are interlocked to prevent opening when the switch is ‘on’.
61GNC 63GNC
SPSN 63
63SB4 SB3 & SB4 63MLK
22
30
TPN
64GC
TPSN
101GNC 103GNC
SPSN 100
100SD5 SB3, SB4, SO & SD5
100MLK 22
30
TPN
104GC
TPSN
151GNC 153GNC
SPSN 160
160SF6 SF3 & SF6 200MLK 90
125
TPN
154GC
TPSN
Part No.
Nominal Unit
Nominal Rating, Ie AC21 (A)
Copper Switch Links Fitted
Motor Ratings AC23A Ue 415V kW HP
201GNC 203GNC
SPSN 200
200SF6 SF3 & SF6 200MLK 90
125
TPN
204GC
TPSN
63GNL 103GNL
63
125 125
63MLK 100MLK
22 22
30 30
303GNC
TPN
315
315SF7 SF3 & SF7 400MLK 110
150
100
304GC
TPSN
-
160 (Use 200A Switch-Disconnector)
-
-
-
-
403GNC
TPN
400
400SF8 SF3 & SF8 400MLK 110
150
404GC
TPSN
203GNL
200
315
200MLK
90
125
503GNC 603GNC
TPN TPN
500 630
500SH9 SH8 & SH9 630MLK 225
300 300
-
315 (Use 400A Switch-Disconnector)
-
-
-
-
630SH9
-
630MLK 225
604GC
TPSN
403GNL
400
630
400MLK
110
150
803GNC
TPN
800 800SH10 SH8 & SH10 800MLK 300
400
-
500 (Use 630A Switch-Disconnector)
-
-
-
-
804GC
TPSN
* If DP fuse-switch-disconnectors are required, use SPSN and replace the supplied switch link with a compatible fuselink. Stud size: 63/100A = tunnel terminal, 160/200A = M10, 300/400 = M14, 500/800A = see page 148, “copper terminal plate”
603GNL 803GNL
630 800
1000 1000
400MLK 800MLK
225 300
300 400
Exel 2 Switch-Disconnectors & Switch-Disconnector Fuses
Part No.
Poles Utilisation Category at Ue 415V to BS EN 60947-3
250V DC Rating to BS5419 DC23 (A)
Blank Endplate
AC22A (A) AC23A (A)
-
SPSN
20
11
201)
EP 842
15AXD2 15AXTN2
DP
TPN
-
SPSN
32
22
32
-
30AXD2 30AXTN2
DP
TPN
Exel 2 switch disconnectors and switch-disconnector fuses meet the constructional requirements for isolation of and are type tested to BS EN 60947-3. Switches are of the quick make and break type, suitable for use on AC or DC. Units have removable moving contact assemblies to facilitate wiring. Exel 2 surface-mounting enclosures are fabricated from rust-protected sheet steel with a light grey paint finish. Removable blank top and bottom end plates (except for 20 and 32A top end plates which incorporate knockouts) and gasket doors give IP41 protection. Chromium-plated front operated handles, with “ON (I) OFF (O)” indication, and internal fixing enabling units to be mounted closely side by side. Interiors comprise porcelain bases fitted with non-ferrous conducting components.
-
SPSN
63
-
63
EP 539
60AXD2 60AXTN2
DP
39
TPN
-
SPSN
100
-
100
-
100AXD2 100AXTN2 125AXTN2
DP
52
TPN TPN
125
52
-
-
SPSN indicates switched neutral. 1) 20A units are DC22.
300
Together we GENERATE VALUE
Made with FlippingBook - Online magazine maker