Bell Lighting Guide 2026

173

Twin Spot Spacing Tables

09159 Anti Panic Area (0.5 lux minimum)

Transverse

Axial

Beam

Mounting Height (M)

Transverse Spacing (m)

Axial Spacing (m)

Beam Separation

To Wall (m)

To Wall (m)

2

2.5

5

2.5

6.5

90°

2.5

3

6.7

4

8.7

90°

3

3.5

8.3

4

10

90°

4

4.5

11

5

15.5

90°

5

5.5

14

7.5

20

90°

6

6

15

8

24.5

90°

8

6.5

16

9

27

90°

10

6.8

17

9

28

90°

12

8.5

20

12

39

60°

15

9

22.5

14

40.5

50°

20

9

25

15

40

30°

09159 Anti Panic Area (1 lux minimum)

2

2.5

5

2.5

6.5

90°

2.5

4

8.7

3

6.7

90°

3

3.5

8.3

4

10

90°

4

4.2

10.5

5

15.5

90°

5

4.5

11

8

19

90°

6

4.5

10.5

9

23.5

90°

Transverse to Transverse

Transverse to Wall

8

4.5

12

9

25

90°

Axial to Axial

Axial to Wall

10

4.2

12

9

26

90°

12

7

17

10

29.5

60°

15

9

21

10

31

50°

20

8

25

10

32

30°

091592 Escape Route (1 lux minimum)

2

-

-

5.5

13.2

90°

2.5

-

-

7

17.2

90°

90°

3

-

-

8.7

21

90°

4

-

-

11.5

27

90°

5

-

-

12.5

31

90°

6

-

-

13.5

33.5

90°

8

-

-

15

38

90°

10

-

-

15

41

90°

12

-

-

16

42

80°

15

-

-

16.5

44.5

80°

20

-

-

16

45

70°