Bell Lighting Guide 2026

172

Twin Spot Spacing Tables pectrum S

09088V2 Anti Panic Area (0.5 lux minimum)

Transverse

Axial

Beam

Mounting Height (M)

Transverse Spacing (m)

Axial Spacing (m)

Beam Separation

To Wall (m)

To Wall (m)

2

4.2

9

4.2

12

90°

2.5

4.6

11

5.6

15

90°

3

4.8

12

5.8

16.2

90°

4

5

13.2

6.3

18

90°

5

5.2

14

7

19

90°

6

5.4

15.3

7

20.1

90°

8

5.2

16

7.5

23.5

90°

10

4.8

16.8

7

25

90°

12

4.5

16.8

6.2

26

90°

15

4

18

5

26.5

60°

20

3

16

4

25

60°

09088V2 Anti Panic Area (1 lux minimum)

2

3.5

8.2

4

10

90°

2.5

3.5

9

4.5

16

90°

3

3.5

9.5

4.5

16.5

90°

4

4

10.5

4.8

14.5

90°

5

4

11

5

15

90°

Index

6

4

11.5

5

16

90°

Transverse to Transverse

Transverse to Wall

8

3.5

12

5

16

90°

Axial to Axial

Axial to Wall

10

3

11

4

14.5

90°

12

2

10

3

14

90°

15

3

10

3

12

60°

20

2

8

3

9

60°

09088V2 Escape Route (1 lux minimum)

2

-

-

5

12.5

90°

2.5

-

-

5.5

13.5

90°

90°

3

-

-

5.8

14.8

90°

4

-

-

6.3

16.3

90°

5

-

-

6.5

17.5

90°

6

-

-

6.8

18.3

90°

8

-

-

5.8

19

90°

10

-

-

5.5

18

60°

12

-

-

5

17

40°

15

-

-

3

15

20°

20

-

-

0.8

7

0°