Bell Lighting Guide 2023
Emergency Lighting
pectrum S Downlight Spacing Tables
270
3W Open Area Recessed Downlight (09030) Spacing Table Open Area (0.5 lux minimum)
Mounting Height (M)
Transverse To Wall (M)
Transverse To Transverse (M)
Axial To Wall (M)
Axial To Axial (M)
2.5
3
7.8
-
-
4
3.6
9
-
-
6
3.6 - 3W Corridor Recessed Downlight (09031) Spacing Table Escape Route (1 lux across central line) 10.8 -
Mounting Height (M)
Transverse To Wall (M)
Transverse To Transverse (M)
Axial To Wall (M)
Axial To Axial (M)
2.5
3
7.2
-
-
4
2.4
7.8
-
-
6
-
-
-
-
3W Corridor (09065) Spacing Table Escape Route (1 lux across central line)
Mounting Height (M)
Transverse To Wall (M)
Transverse To Transverse (M)
Axial To Wall (M)
Axial To Axial (M)
2.5
3.8
7.2
-
-
4
5.0
10.8
-
-
6
-
-
-
-
3W Open Area (09065) Spacing Table Open Area (0.5 lux minimum)
Mounting Height (M)
Transverse To Wall (M)
Transverse To Transverse (M)
Axial To Wall (M)
Axial To Axial (M)
Index
2.5
3.2
6.6
3.2
6.6
4
3.8
9
3.8
9
6
3.6
11.2
3.6
11.2
Transverse to Transverse
Transverse to Wall
Axial to Axial
Axial to Wall
www.belllighting.co.uk
Made with FlippingBook Online newsletter creator