Bell Lighting Complete Guide 2024
Emergency Lighting
Emergency Lighting
pectrum S Bulkhead Spacing Tables
Bulkhead Spacing Tables pectrumPro S
268
269
7W High Power Bulkhead (09094V2) Spacing Table Escape Route (1 lux across central line)
3W Bulkhead (09040V2) Spacing Table Escape Route (1 lux across central line)
Mounting Height (M)
Transverse To Wall (M)
Transverse To Transverse (M)
Axial To Wall (M)
Axial To Axial (M)
Mounting Height (M)
Transverse To Wall (M)
Transverse To Transverse (M)
Axial To Wall (M)
Axial To Axial (M)
4
7
16
7
16
2.5
4.5
9.4
3.5
6
6
8
20
8
20
4
4.5
10
3.5
6.5
8
8.5
22
8.5
22
6
4.5
9.5
2.5
5.5
Open Area (0.5 lux minimum) Spacing Table
Open Area (0.5 lux minimum) Spacing Table
Mounting Height (M)
Transverse To Wall (M)
Transverse To Transverse (M)
Axial To Wall (M)
Axial To Axial (M)
Mounting Height (M)
Transverse To Wall (M)
Transverse To Transverse (M)
Axial To Wall (M)
Axial To Axial (M)
4
6.5
16.5
6.5
16.5
2.5
4
9
3.5
8
6
7.5
18.5
7.5
18.5
4
5
10
4
9
8
8.5
23.5
8.5
23.5
6
5
11.5
4
10
Transverse to Transverse
Transverse to Wall
Transverse to Transverse
Transverse to Wall
Axial to Axial
Axial to Wall
Axial to Axial
Axial to Wall