Airflow Solutions main catalogue
Duplexvent FLEXI DV3600 Flexi Line Side Entry - Up to 3800 m 3 /hr air volume Key Features
Casing Strength EN 1886, mm/m
Energy Efficiency Eurovent
A B C D E F
10 4 0
D3 D2 D1͚
1
● Extract up to 3600 m³/hr @ 200 Pa ● Excellent heat recovery efficiency, up to 95% ● Versatile unit positioning with floor and ceiling suspended mounting options ● Low SFP with energy saving EC fans ● Low noise, refer to NR35 and BB93 standards ● 10 speed digital control with internet and BMS ● Compliant to BREEAM, Passive House and ErP 2015 regulations ● 2 year warranty +
CERTIFIED COMPONENT Passive House Institute
10 %
20 %
30 %
40 %
50 %
30
Supply
100 % 90 % 80 % 70 % 60 %
e1 - outdoor air (ODA) e2 - supply air (SUP) Winter Operation*:
t [°C]
Description t [ o C] rh [%] e1 Outdoor Air -10.0 90 e2 Supply Air 18.0 11
25
i1 - extract air (ETA) i2 - exhaust air (EHA)
i1
20
e2
exhaust air
supply air
400 V 0.45 kW
400 V 0.40 kW
15
50
45
Exhaust
2000 m 3 /hr 250 Pa 19°C 11%
1°C 100 %
18°C 11 %
40
e2
i2
heat recovery -19.4 kW
B
1°C 97%
10
35
Description t [ o C] rh [%] i1 Extract Air 22.0 40 i2 Exhaust Air 1.0 100
h [kJ/kg]
30
1200
25
Mi.103.EC3
5
Me.103.EC3
S4.A.H 88 % 19.4. kW
Performance
heat recovery 19.4 kW
20
Extract Supply
15
0
2000 m 3 /hr 250 Pa 22°C 40%
1000
i2
10
-10 °C 90%
-5
22° 40 %
-10°C 90 %
5
e1
i1
800
filtration M5
filtration F7
0
extract air
outdoor air
Sound Power Level Lw (dB) dB (A) 63 125 250 500 1k 2k 4k 8k Outdoor air e1 50 67 65 46 36 35 28 <25 <25 Supply air e2 70 71 83 72 62 61 54 48 53 Extract air i1 50 66 65 45 38 34 28 <25 <25 Exhaust air i2 69 69 82 71 61 59 53 47 52 Breakout noise 54 56 67 56 49 44 35 <25 <25 Sound Pressure Level Ld dB (A) 63 125 250 500 1k 2k 4k 8k To the surrounding 33 36 46 36 28 <25 <25 <25 <25
-10
-5
e1
Note: AHU functions diagram. Inlet and outlet location may differ from actual position and port configuration.
0 1 2 3 4 5 6 7 8 9 101112131415 x [g/kg of dry air] -15
600
400
STATIC PRESSURE (Pa)
●
200
10 %
20 %
30 %
40 %
50 %
30
100 % 90 % 80 % 70 % 60 %
Supply
e1 - outdoor air (ODA) e2 - supply air (SUP) Summer Operation*:
t [°C]
0
i1 heat recovery i2 -2.3 kW
e1 e2
25
heat recovery 2.3 kW
Description t [ o C] rh [%] e1 Outdoor Air 22.0 35 e2 Supply Air 25.0 29
i1 - extract air (ETA) i2 - exhaust air (EHA)
0
250
500
750
1000 1250
l/sec
20
Sound pressure level is measured at 3m distance
0
500 1000 1500 2000 2500 3000 3500 4000 4500
m /hr 3
AIR FLOW
supply air
exhaust air
15
50
400 V 0.45 kW
400 V 0.40 kW
1500
45
Ventilation
Supply Air
Extract Air
Exhaust
23°C 61%
25°C 29%
2000 m 3 /hr 250 Pa 26°C 28%
40
e2
i2
B
10
35
23°C 60%
Description t [ o C] rh [%] i1 Extract Air 26.0 50 i2 Exhaust Air 23.0 61
Maximum air volume @ 200 Pa
m 3 /hr / l/sec 3600 / 1000 3600 / 1000
30
h [kJ/kg]
1250
25
5
Me.103.EC3
Mi.103.EC3
S4.A.H 84 % -2.3 kW
20
Air volume @ 250 Pa *
m 3 /hr / l/sec 2000 / 556
2000 / 556
15
1000
0
2000 m 3 /hr 250 Pa 26°C 50%
10
Nominal voltage
V
400 400
400 400 397 2.4 M5 EC 1480
22°C 35%
-5
5
Voltage (at operation point) * Nominal Power (at operation point) *
26°C 50%
22°C 35%
i1
e1
V
750
0
filtration M5
filtration F7
-10
extract air
outdoor air
W 446 W 1480
-5
500
Max connection power
0 1 2 3 4 5 6 7 8 9 101112131415 x [g/kg of dry air] -15
Note: AHU functions diagram. Inlet and outlet location may differ from actual position and port configuration.
● ●
Max current
A
2.4 F7 EC
NOMINAL POWER (W)
250
Extract Supply
Filters
Dimensions
Fan type
0
0
250
500
750
1000 1250
l/sec
* Note: ● The figures above have been measured at 2000 m 3 /hr and 250 Pa. Please use the Duplexvent Selection Software to calculate measurements at other performance levels.
Front View
Right
Left
0
500 1000 1500 2000 2500 3000 3500 4000 4500
Connections
Type
Diameter
Accessories
780
2450
780
m /hr 3
163
300
AIR FLOW
300
163
370x275
1040
e1 e2
Outdoor Air Supply Air Extract Air Exhaust Air
600 x 300 mm Shut-off Damper, Flexible Connector
100
Heat Recovery
Supply Air
Extract Air
140
140
600 x 300 mm 600 x 300 mm 600 x 300 mm
Flexible Connector Flexible Connector Flexible Connector
140
145
145
Maximum air volume @ 200 Pa
m 3 /hr / l/sec 3600 / 1000 3600 / 1000
i1 i2 K
90
e2
i2
● ●
600
600
i1 600x300 145 75 600x300
600x300 145
Air volume @ 250 Pa * Temperature at inlet * Temperature at outlet * Humidity at inlet * Humidity at outlet *
m 3 /hr / l/sec 2000 / 556
2000 / 556
Condensate Outlet
Ø 21 mm Condensate Trap
80
1660
O C O C
-10
22
18 90 11
1
70
e1
600
600
%rh %rh
40
75
75 600x300
75
K
K
K
60
150
150
150
100
163
300
163
300
Thermal efficiency in winter / summer Performance in winter / summer
%
88 / 84
Top View
Accessories See Duplexvent accessories pages 204-206 for more details.
50 THERMAL EFFICIENCY %
Winter Summer
kW
19.4 / -2.3
Condensation
l/h
6.5
0
Weight = 320kg
0
250
500
750
1000 1250
l/sec
Type of heat exchanger
Counter Flow, Plastic
1040
370 x 275
P art No.
90000070
0
500 1000 1500 2000 2500 3000 3500 4000 4500
m /hr 3
* The above figures are example performance measurements. Please use the Duplexvent Selection Software to calculate measurements at other performance levels.
* Note: ● The figures above have been measured at 2000 m 3 /hr and 250 Pa. Please use the Duplexvent Selection Software to calculate measurements at other performance levels.
AIR FLOW
+ Excludes motors
airflow.com
Customer Services 01494 560800
airflow.com